Air Cooled Package Chiller With Tank and Pump DAVP1253

12.5 Ton – DAVP1253 – 208-230/3/60

Standard Features

  • Heavy duty welded, tubular steel frame with high gloss powder coat finish and laminated polyethylene cabinet
  • U.L. Listed, and EPA Compliant, eco-friendly R410a refrigeration condensing unit
  • Single refrigeration circuit with Copeland scroll compressor with crankcase heater
  • Air cooled, high ambient, vertical discharge, condensers for 100°F ambient with fan cycle control
  • Weather proof electrical panel with single point power connection and 24 vac control circuit
  • Remote control panel for indoor installation provides lighted on/off switches and digital thermostat
  • High performance coaxial evaporator with inner copper tubing and protective steel shell. UL and ASME listed coil is insulated against condensation with expanded foam
  • Externally equalized thermal expansion valve, liquid line filter drier, and sight glass
  • Low water flow compressor interlock safety locks out compressors in low flow condition
  • Non-ferrous water lines with FPT connections insulated with 1/2” closed cell insulation
  • 26 gallon, high density, polyethylene reservoir insulated with 1/2” closed cell insulation
  • High head centrifugal process pump rated at 40 psi at 2.5 GPM/ton
  • Warranty: one ( 1 ) years limited parts, five ( 5 ) years limited compressor warranty
  • Systems leak checked, pressure tested, run tested under load and shipped operation ready.

Options & Accessories

  • Receivers for 90% refrigerant storage (heated and insulated for temperatures below
  •  30°F ambient)
  • Condenser coil coating for corrosion protection in coastal areas
  • Fan speed control to maintain steady head pressure in cold ambient
  • Voltage and phase monitor in 2 through 7.5 ton
  • Cabinet mounted glycerin filled fluid supply pressure gauge
  • Cabinet mounted, glycerin filled refrigeration pressure gauges
  • Cabinet mounted, analog fluid inlet and outlet gauges
  • Inhibited propylene glycol concentrate or 65% / 35% premix in 55 gallon drums or 5 gallon carboys
  • Castors for portability
  • Factory authorized technician for startup and training

download-now-button

Recirculating---Air-Cooled-Chiller-(with-Tank-and-Pump)

Electrical Data
Power Supply:  208-230/3/60
Compressor: LRA: 2 @ 149 Amps
RLA: 2 @ 22.4 Amps
Fan Motor: FLA: 2 @ 4.8 Amps
Pump Motor: H.P. 1.5
FLA: 10 Amps
Total Circuit: FLA: 59.6 Amps
MCA: 74.5 Amps
MOP: 80  Amps

 

Physical Data
Dimensions: 66”L x 44”W x 74”H
Ship  Weight: 1575 lbs.
Minimum Clearances: 30” All Sides   60” above Top
Noise Rating: 77 dBA @ 10 feet
Fans CFM: 8000 cfm @ 125°F
Tank Capacity: 100 Gallons ( Atmospheric )