5 HP Brewery Glycol Chiller

5 HP – CAVCS050_BC-K

Brewery Glycol Chiller For 28F Degree Water / Glycol Mixture


Standard Features 

  • Electrical: Single point power connection to weather proof electrical panel allows for quick installation. 24 vac control circuit provided from transformer
  • Controls & Safeties: Compressor high and low refrigeration pressure safeties, anti-short cycle time delay, water flow safety switch and freeze stat. Microprocessor based digital controls with interlocks for low flow and high supply temperature
  • Low Ambient Control: Hot gas head pressure control (flooded condenser) for low ambient operation for winter operation down to -20F degrees
  • Phase Monitor: protects chiller from phase unbalance, phase loss, phase reversal, under voltage, over voltage and provides a memory of the most recent 25 faults
  • Remote control panel with temperature controller, pump on/off and chiller on/off switch
  • Refrigeration: R-404a system with all copper refrigeration lines; liquid line solenoid valve, site glass and moisture indicator, filter dryer, externally equalized thermal expansion valve and service valves on liquid and suction lines
  • Compressor: Hermetic scroll compressor with crankcase heater, suction gas cooled motors, and factory installed solid state external overload protection
  • Air Cooled Condensers: Energy efficient PSC fan motor, high efficiency enhanced tube and fin condenser design, sized for capacity at 95°F ambient. Fan blades are dynamically balanced and TEAO all weather fan motors. Low ambient control is flooded condenser for operation down to –20F ambient
  • Evaporator: High efficient stainless steel brazed plate with UL and ASME listing; insulated against condensation with 3/4” closed cell insulation
  • Process Pump: Single, high head centrifugal pump with insulated wet end
  • Reservoir: oversized glycol reservoir
  • Cabinet mounted sight glass tank level indicator
  • Internal Bypass: Adjustable internal bypass for temperature stability and to eliminate possibility of pump deadheading during low flow situation
  • Includes brass wye strainer shipped loose for installation in a location convenient for routine maintenance cleaning
  • Shipping: ships on a pallet, fully crated to minimize risk of shipping damage
  • Chillers are run tested at factory and shipped charged with refrigerant
  • Warranty: one (1) year limited parts, five (5) years limited compressor warranty

Optional Accessories

  • Condenser coil coating for corrosion protection in salt air environments
  • Cabinet mounted fluid pressure and temperature gauges and refrigeration pressure gauge
  • Inhibited propylene glycol concentrate in 55 gallon drums or 5 gallon carboys
  • Magnum microprocessor controller; BAS compatible. Monitor / control your glycol chiller from a remote computer
  • Dual pumps with lead/lag control; if a pump fails, the back up pump automatically switches on
  • Castors for portability; makes small, indoor units easy to move around
  • R407a and R407c refrigerants;
  • Magnum Brewery Control Panel; gives Brewmaster full control of brewery system. Controls, monitors & records vessel solenoid valves from a computer.

download-now-button

7HP Package American Brewery Chiller 98

Nominal 40,160 Btu/hr @ 28F LFT / 95F Ambient
Dimensions: 46”L x 35”W x 68”H
Ship / Oper. Wt: 925 lbs. / 1,250 lbs.
Minimum Clearances: 30” All Sides
Tank Capacity: 50 Gallons
Connections: 1.25” FPT SUPPLY & RETURN

 

Electrical Data
Power Supply:  208-230/1/60 – Single Phase
Compressor: LRA: 175 Amps
RLA: 31.1 Amps
Fan Motor: FLA: 1 @ 2.1 Amps
Pump Motor  H.P. 1.0
  FLA: 7.4 Amps
Total Circuit: FLA: 40.6 Amps
MCA / MOP: 51 / 70 Amps

 

Electrical Data
Power Supply:  208-230/3/60
Compressor: LRA: 128 Amps
RLA: 22.1 Amps
Fan Motor: FLA: 1 @ 2.1 Amps
Pump Motor  H.P. 1.0
  FLA: 3.6 Amps
Total Circuit: FLA: 27.8 Amps
MCA / MOP: 35 / 50 Amps

 

Electrical Data
Power Supply:  460/3/60
Compressor: LRA: 63 Amps
RLA: 9.6 Amps
Fan Motor: FLA: 1 @ 1.1 Amps
Pump Motor  H.P. 1.0
  FLA: 1.8 Amps
Total Circuit: FLA: 12.5 Amps
MCA / MOP: 16 / 30 Amps
Information provided is subject to change at manufacturers discretion. Submittals available upon request with purchase order.