American Chillers and Cooling Tower Systems

Manufacturer of industrial process chillers
for medical, dry cleaning, aerospace,
food processing and more...

More about us >>

Portable Air Cooled Chiller (with Tank and Pump) CAVSS0754-TZ

7.5 Ton – CAVSS0754-TZ – 460/3/60

Standard Features

  • U.L. Listed, and EPA Compliant, R410a refrigeration condensing unit complies with latest codes
  • Single refrigeration circuit with Copeland scroll compressor with crankcase heater
  • Air cooled, high ambient, vertical discharge, condenser for 100°F ambient;
  • Fan cycle control provides head pressure control down to 0°F ambient
  • Weather proof electrical panel with single point power connection to compressor contactor
  • 24 vac control circuit with component sequenced terminal strip for easy troubleshooting
  • Remote control panel with electronic thermostat, digital temperature indicator lighted switches
  • Stainless steel brazed plate evaporators with hot gas bypass capacity control and solenoid valve
  • Externally equalized thermal expansion valve with liquid line solenoid valve, filter drier, sight glass
  • Copper water lines with FPT connections and insulated with 1/2” closed cell prevents condensation mess
  • Water flow safety switch locks out compressor in no flow condition
  • Internal bypass loop to return line prevents compressor deadheading
  • Lifetime, polyethylene reservoir with cabinet mounted fill port and glass tube external level gauge
  • High head, cast iron centrifugal pump with nominal capacity of 2.4 gpm/ton at 100 ft. hd.
  • Cabinet mounted CHWS outlet pressure gauge and analog temperature gauge
  • Powder coated welded steel frame with laminated polyethylene panels
  • Warranty: One (1)  year limited parts, five ( 5 ) years limited compressor warranty
  • Leak checked, pressure tested and run tested under load prior to shipment

Options & Accessories

  • Receivers for 90% refrigerant storage
  • Heated and insulated receiver for ambient temperatures below 30°F
  • Nonferrous piping in lieu of copper for de-ionized water or corrosive fluids
  • Condenser coil coating for corrosion protection in coastal areas and caustic environments
  • Cabinet mounted, glycerin filled refrigeration pressure gauges
  • Sanitary, double wall, evaporator for potable water
  • Inhibited propylene glycol concentrate in 55 gallon drums or 5 gallon carboys
  • Closed system reservoir in lieu of open polyethylene
  • Factory authorized technician for startup and training
  • Factory authorized contractor for installation
  • Castors for portability

download-now-button

Recirculating---Air-Cooled-Chiller-(with-Tank-and-Pump)

Electrical Data
Power Supply:  460/3/60
Compressor: LRA: 100 Amps
RLA: 12.2 Amps
Fan Motor: FLA: 1 @ 1.3 Amps
Pump Motor H.P 1.5
FLA: 3.4 Amps
Total Circuit: FLA: 16.9 Amps
MOP: 25 Amps

 

Physical Data
Dimensions: 48”L x 35”W x 58”H
Ship  Weight: 1322 lbs.
Minimum Clearances: 30” All Sides   60” above Top
Noise Rating: 88 dBA @ 10 feet
Fans CFM: 4700 cfm @ 125°F
Tank Capacity: 40 Gallons ( Atmospheric )
Connections: 1.25” FPT CHWS and CHWR